Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM00905
Parcel: 13734001A

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T10CM00905
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the revisions to the refrigeration circuits; revisions 1, 2, and 3 have not been submitted for review. Reference: Section 106.3.1, IMC 2006.
09/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide copies of the revised sheets GP1.1 and GP1.2. Reference: Section 103.2.3, UPC 2006.
09/29/2010 GERRY KOZIOL WWM REVIEW Denied NEED TO PROVIDE APPROVED STAMPED WASTE WATER PLANS AS REFERENCE
09/29/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved delta 6 revision to plan

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
10/13/2010 SUE REEVES REJECT SHELF Completed