Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T10CM00905
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the revisions to the refrigeration circuits; revisions 1, 2, and 3 have not been submitted for review. Reference: Section 106.3.1, IMC 2006. |
| 09/27/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide copies of the revised sheets GP1.1 and GP1.2. Reference: Section 103.2.3, UPC 2006. |
| 09/29/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO PROVIDE APPROVED STAMPED WASTE WATER PLANS AS REFERENCE |
| 09/29/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | delta 6 revision to plan |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/13/2010 | SUE REEVES | REJECT SHELF | Completed |