| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/14/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/15/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 1650 W Valencia, Walmart T10CM00905- Revisions Electrical plans for this project denied for the following: 1. Sheet E-4 shows Transformer T4D (150 kva) feeding disconnect ECB-L4D3 with 4-250 mcm cu  grd, good for 250 amps, Panel L4D3-1 has a demand load of 121 amps Panel L4D3-2 has a demand load of 36 amps Panel L4D3-3 has a demand load of 243 amps total 400 amps on the feeder allowing 255 amps fused at 250 amps ? 2. Provide a discription of Panels L4D3-1,2, and 3. Are these feed thur individual panels, are they listed and approved ? Could the panel assembly be all one unit with only one feeder ? 3. Sheet E4.4 shows Panels L4D1 and L4D2 as existing, they should be L4D3-1 and 2. The same panels are shown as -new on Sheet E4 however shown as existing in Panel Schedules Sheet E4.4 Ray T Majuta, Elect Pln Ck, PDSD, City of Tucson, 7/18/10 Ray.Majuta@tucsonaz.gov |
| 07/20/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved |