Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00905
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/13/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Walmart - 1650 W. Valencia Road T10CM00905 Building Plan (1st Review) TRANSMITTAL DATE: April 13, 2010 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. There is a proposed expansion of the tire storage area. Provide a revised development plan that addresses parking area access lane widths adjacent to the expansion. 3. There is a proposed expansion of the tire storage area. Provide a revised development plan that addresses any additional parking required for the expansion. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t10cm00905.doc |
| 04/15/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/15/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET C1; GENERAL NOTE 4: NEW STORAGE RACKS REQIRE A SEPARATE PERMIT. RACKS BETWEEN 6' AND 12' TALL REQUIRE DETAILS ON THE DRAWINGS INDICATING THE METHOD OF CONNECTION TO THE FLOOR SLAB. RACKS OVER 12' TALL REQUIRE STRUCTURAL CALCULATIONS AND PERTINENT DETAILS ON THE DRAWINGS. 2. SHEET GC1; GARDEN CENTER SHADE STRUCTURE: PROVIDE THE MANUFACTURER'S DESIGN INFORMATION FOR THE SHADE STRUCTURE FRAMING. PROVIDE PERTINENT DETAILS ON THE DRAWINGS. 3. SHEET GC1; GARDEN CENTER SHADE STRUCTURE: PROVIDE STRUCTURAL CALCULATIONS FOR THE GARDEN CENTER SHADE STRUCTURE FOOTINGS. PROVIDE PERTINENT DETAILS ON THE DRAWINGS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/15/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 04/16/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a direct connection to the drainage system of the building for the emergency eyewashes (i.e. no indirect connection as shown in detail 5/P2). Reference: Section 304.0, UPC 2006. 2. Provide information to show that the hub drain (detail 9/P2) complies with Sections 411.1 and 804.1, UPC 2006. 3. Appliances (e.g. ovens, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 4. Keynote 15.400/P1 calls for the installation of a hose bibb 24" below the roof deck and upside down. Clarify how this installation conforms to the requirements of Sections 310.4 and 603.4.7, UPC 2006. 5. Provide indirect waste piping for the prep sink. Reference: Section 801.2, UPC 2006. 6. Provide direct waste connections for the wash and rinse sections of the 3-compartment sinks, with indirect connections for the sanitizing compartments only. Reference: Sections 304.0 and 801.2.3, UPC 2006. 7. Sump pumps in public use occupancies are required to have dual pumps. Reference: Section 710.9, UPC 2006. 8. Provide sump pump controls (e.g. visual and audible alarms, etc.) per Section 710.9, UPC 2006. 9. Provide justification for the use of a combination waste and vent system on a grease waste system. Reference: Section 910.1, UPC 2006. 10. Each vent for a combination waste and vent system shall be at least one-half of the cross-sectional area of the pipe being vented. The vent connection shall be downstream of the uppermost fixture. Reference: Section 910.3, UPC 2006. 11. An accessible cleanout shall be installed in each vent for a combination waste and vent system. Reference: Section 910.6, UPC 2006. 12. Vertical waste pipes (e.g. waste pipe from a hand sink) may not be connected with a combination waste and vent system through the use of vertical wet venting: they may be connected with the combination waste and vent system through the use of conventional waste and vent piping. Reference: Section 910.7, UPC 2006. 13. Provide the developed pipe length used for sizing the addition to the existing gas piping system and all of the existing gas loads. Reference: Section 1209.1.2, UPC 2006. |
| 04/19/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The 2006 International Mechanical Code with Local Amendments is the relevant code for the installation of the kitchen hoods. 2. Revise the size of the condensate drains (as shown on sheets MP1.1 and M3) in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. 3. Clarify the wall construction and the wall finishes adjacent to the Type I hoods to show that the hood installations comply with Section 507.9, IMC 2006 for clearances. 4. Note: with regard to the submitted Mechanical Compliance Certificate, the location of this existing Wal-Mart store is less than 4,000 feet in elevation, not greater than 4,000 feet. |
| 04/23/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/03/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM00905, 1650 W Valencia, Walmart TI The Electrical plans have been denied for the following: 1. Sheet E 4, the MSW Main Switchboard shows a new Section # 5 being added. The new section also has at the lower end , existing HB4 Section with a new concrete pad to be installed. Provide information on this new Section. Why is this being added, will this new section if being added be listed with the existing equipment, and how is existing HB4 involved ? 2.Sheet E1.2 , the 36 fixtures being replaced in the Garden Center Area , with new fixtures now appears to come under the 2005 City of Tucson Outdoor Lighting Ord., # 10135. These do not appear to be under a canopy, thus they would be required to be calculated as unshielded, and be Full Cut Off type. Please review this Ordinance for compliance and submit information. 3. The loads on individual panels have been reviewed for the 125% addition of fixtures on for continuous duty. The additional loads appear to be figured, but how have they been added to total ? 4.Sheet E 4.6 , "Connected Loads Table", how is the negative value for lighting(- 46KVA), and negative value for Refrigeration(- 25KVA) obtained ? Provide method of obtaining. 5. Provide a total load based on 2005 NEC 220.87 which is current, with dates of when approved , adding these new values , new loads or negative values Ray T Majuta, PDSD, City of Tucson, Elect Plan Review, 5/3/10 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 05/12/2010 | SUE REEVES | REJECT SHELF | Completed |