Review Details: COMMERCIAL NEW

Permit Number - T10CM00865
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
04/01/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
04/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10CM00865
2585 E 36 th St
Solar Photovoltaic System

Electrical plans for this project denied for following:

1. NEC 2005, 690.14.C, indicates the grouping of disconnecting means for the Photovoltaic system to be grouped with all other disconnecting means of system. This plan shows the Inverter in a different location from service. In this case Section D of the same code requires items 1 thur 4 apply. These do not apply on the plan.
2. Connection to the Utility meter not allowed, the Utility company locks the terminations not allowing access.
3. Indicate conductor sizes for the system on Connection Diagram ( for inspectors reference).
4. If Inverter has disconnecting mens for DC and AC provide cut-sheet for verification.

Ray T Majuta
PDSD Tucson
4/05/10
Ray.Majuta@tucsonaz.gov
04/12/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2010 CPIERCE1 OUT TO CUSTOMER Completed