Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T10CM00802
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/15/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Section 904.1, UPC 2006 requires that the building sewer be ventilated with a vent (or vents) having a total cross-sectional area equal to that of the required building sewer. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area. The elephant building sewer will need a 4" vent and the LSS gravity building sewer will need a 3" vent. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/01/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
12/01/2011 | SUE REEVES | REJECT SHELF | Completed |