Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00802
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM00802
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Section 904.1, UPC 2006 requires that the building sewer be ventilated with a vent (or vents) having a total cross-sectional area equal to that of the required building sewer. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area. The elephant building sewer will need a 4" vent and the LSS gravity building sewer will need a 3" vent.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2011 DELMA ROBEY OUT TO CUSTOMER Completed
12/01/2011 SUE REEVES REJECT SHELF Completed