Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T10CM00802
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/26/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the initial portion of the gas main from 1-1/2" to 2"; the maximum load for a 1-1/2" pipe is 412 CFH at 200-feet. [Original comment: Coordinate the gas piping design shown on sheet 1P101 with the gas diagram and meter load as shown on sheet 0P204.] 2. The floor drain, P-7, located in the restroom 108 is still acting as an indirect waste receptor which is not allowed in a restroom. Have you considered terminating the evaporative cooler drain at the floor sink, P-12, located in room 107? [Original comment: Clarify the installation of floor drain P7 in the restroom 108. Keynote 2 calls it a floor sink which is not allowed in a restroom. Reference: Section 804.1, UPC 2006.] |