Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T10CM00802
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/16/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/16/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the gas piping design shown on sheet 1P101 with the gas diagram and meter load as shown on sheet 0P204. 2. Clarify the designation and layout of room 110; it is shown as "Food Service" on sheet 1M101 with a mop sink located northwest of the pony wall but is called "STG" on sheet 1P101 with a mop sink located southeast of the pony wall. 3. Coordinate the plumbing waste and gas plan (1P101) with the waste and vent isometric on sheet 1P201; is the floor drain, P7, located on the southwest side of the building on sheet 1P201 part of the activity? Also, clarify the connection of floor sink P12 in room 107; it is shown differently on sheets 1P101 and 1P201. 4. Clarify the installation of floor drain P7 in the restroom 108. Keynote 2 calls it a floor sink which is not allowed in a restroom. Reference: Section 804.1, UPC 2006. |
| 08/26/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 09/15/2011 | SUE REEVES | REJECT SHELF | Completed |