Permit Number: T10CM00802
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM00802
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/16/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/16/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the gas piping design shown on sheet 1P101 with the gas diagram and meter load as shown on sheet 0P204.
2. Clarify the designation and layout of room 110; it is shown as "Food Service" on sheet 1M101 with a mop sink located northwest of the pony wall but is called "STG" on sheet 1P101 with a mop sink located southeast of the pony wall.
3. Coordinate the plumbing waste and gas plan (1P101) with the waste and vent isometric on sheet 1P201; is the floor drain, P7, located on the southwest side of the building on sheet 1P201 part of the activity? Also, clarify the connection of floor sink P12 in room 107; it is shown differently on sheets 1P101 and 1P201.
4. Clarify the installation of floor drain P7 in the restroom 108. Keynote 2 calls it a floor sink which is not allowed in a restroom. Reference: Section 804.1, UPC 2006.
08/26/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
09/15/2011 SUE REEVES REJECT SHELF Completed