Permit Number: T10CM00802
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00802
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 DAVE MANN FIRE REVIEW Approved
09/13/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Double check valve assemblies are not listed for use in preventing backflow in health-hazard situations and in the case of the various stock watering devices (e.g. the Nelson Drinker), individual points of use shall be separately protected from backflow conditions. Reference: Sections 103.2.3 and 602.3 and Table 6-2, UPC 2006.
09/13/2010 STEVE SHIELDS ZONING REVIEW Approved
09/28/2010 GERRY KOZIOL WWM REVIEW Denied need PCRWRD site plan review- 3rd floor- Engineering 740-6500.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2010 SUE REEVES OUT TO CUSTOMER Completed
11/23/2010 SUE REEVES REJECT SHELF Completed