Permit Number: T10CM00802
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T10CM00802
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Please provide a comment letter describing how each comment has been addressed.

Provide the following data on the site plans. Comments based on OC201.

Please indicate existing fire hydrant location(s), with dimensions to buildings and/or property lines. Refer to City of Tucson amendments to the 2006 International Fire Code (section 508) for spacing and location requirements. The new hydrant is too far from the Ranger Station if it is not sprinklered.

Please show method of supplying fire sprinklers.
07/12/2010 RONALD BROWN ZONING HC REVIEW Passed Project is a COT owned and operated project and has already been reviewed and approved by Eric Newcomb for ADAAG compliance
07/13/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Reid Park Zoo Elephant Exhibit
T10CM00802
Site Plan (2nd Review)

TRANSMITTAL DATE: July 13, 2010

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC). This project has been reviewed for full code compliance for the areas of expansion and modification to the site only.

Until the waiver has been approved Zoning cannot approve the site and/or building plans. Once the waiver has been approved provide the date of approval on the plan. Zoning will provide an over-the-counter review, please call or email to schedule an appointment.
2. D.S. 2-02.2.2.A.4 Based on discussions with staff, provide a vehicle parking calculation based on the area of expansion only, i.e. 256,000 sq. ft of expansion x 30% = 76,800 sq. ft. of new vehicle parking required. Show on the plan that the additional parking is provided.
3. D.S. 2-02.2.2.A.4 Provide a bicycle parking calculation based on new vehicle parking spaces provided.
4. D.S. 2-02.2.2.A.5 The LUC Section shown on Sheet 000.002 under Loading Zone is not correct. Per LUC Section 3.4.5 REQUIRED OFF-STREET LOADING SPACES, Civic Use Group, the LUC Section that governors the required number of loading spaces is 3.4.5.4.
5. D.S. 2-02.2.2.A.5 Zoning acknowledges that for the proposed expansion one (1) 12 x 35 loading space is required, as shown on the calculation. As there is not a new 12 x 35 loading space shown for the expansion provide a loading space calculation that provides the required loading spaces for all square footage of the zoo area and the provided number of loading spaces.
6. Depending on how the above comments are addressed addition comments may be forth coming.
If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t10cm00802

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
07/16/2010 ANDREW CONNOR NPPO REVIEW Approved
07/16/2010 ANDREW CONNOR LANDSCAPE REVIEW Approved
07/26/2010 PAUL MACHADO ENGINEERING REVIEW Approved
07/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/10/2010 SUE REEVES REJECT SHELF Completed