Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00644
Parcel: 11706168A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00644
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2010 MARTIN BROWN FIRE REVIEW Approved
03/17/2010 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
03/18/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/18/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. Mechanical Comment: Provide energy code compliance calculations for the building addition. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for any fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Sheet S2.1; Foundation Plan: The footing near Grids E and 5 is marked as F1 (at future walkway). Should this be an F5? Verify.
3. Sheet S2.1; Foundation Plan: The columns and footings for the future walkway were not found in the structural calculations, but sizes are indicated on the plan. Clarify.
4. Sheet S2.1; Foundation Plan: Most of the columns and footings in the new restroom were not found in the structural calculations, but sizes are indicated on the plan. Clarify.
5. Sheet S3.1; Framing Plan: On Grid 2, above Grid B, there is a B1 beam indicated on the plan. Clarify.
6. Sheet S3.1; Future Walkway: Provide an indication (similar to Sheet S2.1) that the steel frames and beams are shown for reference only and will be designed under separate permit.
7. Sheet S4.1; Roof Plan: The interior spanning beam over the restrooms does not have a size indicated. Provide.
8. Sheet S4.1; Future Walkway: Provide an indication (similar to Sheet S2.1) that the steel frames and beams are shown for reference only and will be designed under separate permit.
9. Structural Calculations; Page 9: Did not locate beams B6 or B8 on this sheet. Clarify.
10. General: Provide written responses to all review comments.
03/18/2010 RMYERS1 WATER REVIEW Approved
03/18/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide "Petition of Appeal" from the building official for use of the IPC.
2. Provide site drawing showing the size, route, and slope of the building sewer. Reference: Section 103.2.3, UPC 2006 Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
5. Revise the termination of the primary rainwater leader so that it doesn't cross over the sidewalk. Reference: Section 4.4 F, City of Tucson Development Standard No. 3-01.0.
6. Revise the termination of the secondary (overflow) rainwater leader so that it terminates above grade in a location observable by the building occupants or maintenance personnel. Reference: Section 1101.11.2.2.1, UPC 2006dard No. 3-01.0.
03/18/2010 GERRY KOZIOL WWM REVIEW Denied need to show location/method of connection to public sewer.
need 3rd floor WWM review/ Chad or Tom- 740-6547
03/18/2010 STEVE SHIELDS ZONING REVIEW Passed Passed per Ernie Duarte direction. Historic review to be completed early next week.
03/18/2010 BIANCA RAMIREZ ENGINEERING REVIEW Passed Engineering passed per Ernie Duarte
03/18/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: 300 E CONGRESS ST, T10CM00644,
RIALTO BLOCK PROJECT

ELECTRICAL PLANS DENIED FOR THE FOLLOWING;

1. SHEET E-2CIRCUITS B 26,28,30,32, ARE USED TWICE ON THE LIGHTING PLAN, CIRCUITS B-23,25,27, SHOWN IN PANEL SCHEDULE NOT ON LIGHTING PLAN.
2. TRACK LIGHTING TO BE CALCULATED PER 150VA FOR EVERY TWO FEET OF TRACK,THEN 25% FOR CONTINUOUS DUTY.

RAY T MAJUTA,ELECT PLN CK
PDSD,CITY OF TUCSON
3/18/10
520/837/4988
03/18/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/18/2010 ERIC NEWCOMB ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
03/19/2010 SUE REEVES REJECT SHELF Completed