Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM00475
Parcel: 12510003G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00475
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/25/2010 RONALD BROWN ZONING HC REVIEW Approved
04/01/2010 ROBERT SHERRY WATER REVIEW Approved
04/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the detail of the "Ariston GL6" water heater installation (1/P-3.0), to include the vacuum relief on the cold water supply. Reference: Sections 103.2.3 and 608.7, UPC 2006.
2. Revise the waste and vent plan (sheet P-2.0) to show the vent for the floor sink located in the Prep Area, in front of the ice machine. Reference: Sections 103.2.3 and 901.0, UPC 2006.
04/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2010 DELMA ROBEY OUT TO CUSTOMER Completed
04/07/2010 SUE REEVES REJECT SHELF Completed