Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00475
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/25/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/25/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
04/01/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the detail of the "Ariston GL6" water heater installation (1/P-3.0), to include the vacuum relief on the cold water supply. Reference: Sections 103.2.3 and 608.7, UPC 2006. 2. Revise the waste and vent plan (sheet P-2.0) to show the vent for the floor sink located in the Prep Area, in front of the ice machine. Reference: Sections 103.2.3 and 901.0, UPC 2006. |
04/05/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |