Permit Number: T10CM00359
Parcel: 125031320

Address:
3039 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM00359
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2010 GERRY KOZIOL WWM REVIEW Approved
05/12/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-13-10
Activity: T10CM00359
Address: 3039 E 4th St
Applicant: Leo Katz

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans including revisions, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:
3. Provide zoning and engineering approval on second site plan or remove from submittal.
4. Provide zoning approval for site walls exceeding six (6) feet in height.

SECTIONS - DETAILS:
5. Provide plan view detail for detail number 2.2.
6. Specify connection of 2x wood hip rafter to tube steel hip beam.
7. Provide detail for fireplace footing.

PLUMBING PLAN:
8. Provide vent piping through the roof so that the aggregate cross-sectional area shall not be less than that of the largest required building sewer, UPC 904.1.
9. Show the size and location of all cleanouts, UPC 707.4, Table 7-6. Two-way cleanout required within 2' from the building at the lower end. Cleanouts are required at the kitchen sink area UPC 707.4 W/ State amendment.
10. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10.

MECHANICAL PLAN:
11. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.

OUTDOOR LIGHTING CODE
12. Clarify outdoor lighting calculation with references to proposed fixture types. Five (5) fixtures shown and only three (3) are on the calculation.
13. Quoizel lighting fixture is not considered fully shielded.

If you have any questions please contact: