Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00311
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/10/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; Section 506.3.12.3, IMC 2006 requires the fan to be located not less than 10'-0" from parts of the same or contiguous building and air intakes into any building. The exception allowing the fan to be within 5'-0" of the building is not applicable in this case since the fan discharge is not directed away from the building but parallel to the building. Show that the termination of the grease exhaust fan complies with the requirements of Section 506.3.12, IMC 2006. See also Sections 304.10 and, if the slope of the metal roof is 3/12 or greater, Section 306.5.1, IMC 2006 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/13/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |