Permit Number: T10CM00311
Parcel: 11504492A

Address:
901 E 1ST ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00311
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; Section 506.3.12.3, IMC 2006 requires the fan to be located not less than 10'-0" from parts of the same or contiguous building and air intakes into any building. The exception allowing the fan to be within 5'-0" of the building is not applicable in this case since the fan discharge is not directed away from the building but parallel to the building. Show that the termination of the grease exhaust fan complies with the requirements of Section 506.3.12, IMC 2006. See also Sections 304.10 and, if the slope of the metal roof is 3/12 or greater, Section 306.5.1, IMC 2006

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2010 DELMA ROBEY OUT TO CUSTOMER Completed