Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM00311
Parcel: 11504492A

Address:
901 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM00311
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2010 RONALD BROWN ADA REVIEW Passed
06/14/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Sheet 3
Door 9 requires panic hardware per IFC Section 1008.1.9.
06/15/2010 STEVE SHIELDS ZONING REVIEW Approved
06/18/2010 RONALD BROWN ZONING HC REVIEW Approved
06/18/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide a scaled plan of the existing building floor plan showing demolition as well.
a. Please identify all the rooms
b. Please provide an occupancy load calculation of the existing facility prior to the classroom additions and modifications.
2. Please provide completed Special Inspection Certifications for the following:
a. Epoxy Anchors
b. Expansion anchors
c. Anchor bolts in concrete
d. Structural masonry
and any others deemed necessary by the Structural Engineer.
3. At Sheet 3, what is Note number 8 in the kitchen all about? This is not shown in structural drawings.
4. Provide panic hardware at all exist doors as required by section 1008.1.9.
5. All sheets that have lettering smaller tham 3/32" must be revised and resubmltted to meet the minimum font size requirement.
END OF REVIEW
06/22/2010 ROBERT SHERRY WATER REVIEW Approved
06/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations (Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Show how the fan coil is connected to the building structure and how maintenance access will be provided to the fan coil (the fan coil appears to be bisected by the partition support shown in detail 1 on sheet 6). Reference: Sections 302.1 and 306.1, IMC 2006.
3. Show the routing and termination of the condensate drains for the fan coil and the ductless heat pump. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
4. Clarify how and to where the auxiliary drain pan for the fan coil unit will be drained. Reference: Section 307.2.3 IMC 2006.
5. Provide calculations demonstrating adequate ventilation for the enlarged classroom. Reference: Section 401.2, IMC 2006.
6. Clarify if the kitchen shown on the plans is existing or a replacement for the kitchen being removed on the east side of the building. If the kitchen is new, a Type I grease hood will be required over the range. Reference: Section 507.2.3, IMC 2006.
7. Provide a smoke detector in the return air duct for the fan coil unit, up stream of any outside air connections. Reference: Section 606.1, IMC 2006.
06/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a complete plumbing plan, including waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
2. Indicate the materials to be used in the proposed plumbing systems for this activity. Reference: Sections 103.2.3, 301.1, 604.0, 701.0, 903.0, 1102.0, and 129.5, UPC 2006.
3. Verify that the materials used for the drainage piping in the area of the new classroom are approved for use under the new building addition. Reference: Section 313.4, UPC 2006.
4. Verify the location of the initial cleanout for the existing building sewer and show how it is to be extended to the finished floor grade in the new addition. Reference: Sections 719.1 and 719.3, UPC 2006.
5. Show the plumbing fixtures and drainage fittings installed correctly and in a manner consistent with the Code and the manufacturer's instructions. Reference: Sections 304.0 and 310.4, UPC 2006.
6. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. NSF, UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
06/25/2010 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/28/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/30/2010 GERRY KOZIOL WWM REVIEW Approved
07/07/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review