Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T10BU01146
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: OReilly Auto Parts
T10BU01146
Grading Plan (5th Review)

TRANSMITTAL DATE: August 15, 2011

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not approve the grading plan until the site plan has been approved. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10bu01146

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Grading plan and a copy of the approved site plan
08/22/2011 LOREN MAKUS ENGINEERING REVIEW Denied August 24, 2011
T10CM2007
T10BU01146


1. On the site and grading plans, clearly indicate the extent of the screen wall along the property line.
2. The driveway onto North Arcadia Avenue appears to have a curb return on one side and a sharp curb end on the other. Provide details and dimensions to clarify how the driveway is to be constructed.
3. Clarify the extent of paved area especially in the areas south of the proposed building.
4. The grading plan will not be approved until a floodplain use permit has been approved and associated fees have been paid.

Loren Makus, EIT
Senior Engineering Associate
Loren.makus@tucsonaz.gov
08/22/2011 ANDREW CONNOR NPPO REVIEW Denied The grading plan has been reviewed by the Landscape / NPPO Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/09/2011 SUE REEVES REJECT SHELF Completed