Permit Number: T10BU00039
Parcel: 132130800

Review Status: Completed

Review Details: TANKS

Permit Number - T10BU00039
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

1. Ths Engineers Seals on the plans are not signed.
2. Sheet T-8: The curb height is shown as "varies". It must be 6 inches minimum or bollards at 4 feet oc must be provided.
02/02/2010 STEVE SHIELDS ZONING REVIEW Approved
02/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10BU00039 , 3434 S Kino PW
Fuel Tanks and Dispensers Control Blg
Costco

The electrical plans have been denied for the following:

City of Tucson Summital Requirements require an EE to seal the electrical drawings.To be reviewed and signed by State of Az., EE.

Ray T Majuta, Elect Pln Ck ,
PDS, City of Tucson,
Ray.Majuta@tucsonaz.gov
2/05/10

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2010 SUE REEVES OUT TO CUSTOMER Completed
02/17/2010 SUE REEVES REJECT SHELF Completed