Permit Number: T09OT02215
Parcel: 11713061N

Address:
198 S GRANADA AV

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T09OT02215
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2009 ELIZABETH EBERBACH ENGINEERING REVIEW Approved November 3, 2009

FLOODPLAIN USE PERMIT # T09OT02215
PROJECT ADDRESS: 198 S Granada Av
APPLICANT'S NAME: Clint Glass, PE for Allan Norville
PROPERTY OWNER: Allan Norville, 411 W Congress

The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as:


A portion of Parcel 117-13-061N at 198 S GRANADA AV, Tucson, AZ 85701, in a portion of Township 14S, Range 13E, Section 14,


for the purpose of extending drainage pipe, parking lot fill and improvements, and other drainage improvements including inlet structure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following 8 conditions apply to this permit T09OT02215:
1) Bollards are required around inlet structure.
2) All work shall conform to the approved GRADING PLAN: NORVILLE PROPERTY, TCC WASH CULVERT EXTENSION PROJECT, activity number T09BU01552, by CMG Drainage Engineering, Inc. (dated 10/12/9), hydrologic and hydraulic analyses report: (dated 10/12/9), which is made part of this permit.
3) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T09OT02215. FOR INFORMATION PLEASE CALL 791-5550."
4) Floodplain Engineering inspections are required. Call for Pre-construction meeting and drainage inspections. Contact IVR 740-6970 to schedule a Floodplain or Grading inspection, or PDSD Engineering at 837-4991.
5) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
6) There shall be NO stockpiling north or east of the proposed inlet structure. There shall be NO disturbance outside of the grading limits other than the construction entrance area as specified on the approved plans. Disturbance limits shall be adhered to as shown on the approved plans. Any disturbance activity outside of the limits shall be subject to notice of violation, Stop Work Order, citation, and/or other penalties.
7) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the site development, or, if there is any further disturbance within the floodplain other than that outlined in the approved grading plans or drainage report. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.
8) This permit does not authorize the construction of walls, building pads, or building of other structures other than the required improvements per the approved plans and permits. Any construction shall be authorized by a separate building permit.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire two years from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division.



(EXPIRATION DATE) Month: 11 Day: 3 Year: 2010