Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM03201
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/07/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to include a zone air distribution effectiveness (Table 6-2) of 0.8. Reference: Section 403.2, IMC 2006, as amended by the City of Tucson. 2. Revise the pumped condensate from AC-3 to terminate with an indirect waste connection. Reference: Section 805.0, UPC 2006. |
| 12/07/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/07/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the total connected demand for the water heater; an 8 PSI drop is excessive. Reference: Section 610.2, UPC 2006. |
| 12/07/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A5.0; SECTION 18: CUT A CROSS SECTION THROUGH THE STAIR, INDICATING SIDE WALLS OF THE STAIR TO CONTAIN THE COMPACTED FILL. |
| 12/07/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 12/07/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006. |
| 12/07/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/07/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/07/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/07/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 12/10/2009 | GBONILL1 | WWM | REVIEW | Approved |