Permit Number: T09CM03122
Parcel: 11820072C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM03122
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T09CM03122, provide electrical information on plan,how will pumps be fed?

Ray T Majuta, Elect Plan Ck,
1/11/10
11/25/2009 LOREN MAKUS ENGINEERING REVIEW Approved
11/25/2009 STEVE SHIELDS ZONING REVIEW Approved
12/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate the termination points for the pressure relief and for the temperature/pressure relief valves.
2. Clarify which water heater is being proposed and how it is powered.
3. If the water heater is to be gas-fired, show the required gas piping, combustion air, and the flue sizing and installation details.
4. Show any electrical modifications to the building.
12/01/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/01/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2010 GERARDO BONILLA OUT TO CUSTOMER Completed