Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM03122
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T09CM03122, provide electrical information on plan,how will pumps be fed? Ray T Majuta, Elect Plan Ck, 1/11/10 |
| 11/25/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/25/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/01/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate the termination points for the pressure relief and for the temperature/pressure relief valves. 2. Clarify which water heater is being proposed and how it is powered. 3. If the water heater is to be gas-fired, show the required gas piping, combustion air, and the flue sizing and installation details. 4. Show any electrical modifications to the building. |
| 12/01/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/01/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |