Permit Number: T09CM02912
Parcel: 10503032F

Address:
5055 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02912
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/31/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved. Make up air that is not heated (or cooled) may not be introduced into the kitchen in such a way that it reduces the comfort conditions of the occupied space. Show how the terminations of the ducts from MAU-1 and MAU-2 comply with the requirements of Section 508.1.1, IMC 2006.
2. Comment not resolved. If the make up air ducts are insulated, the insulation within 18" of the Type I hood shall be "… non-combustible or listed for the application." Show that the make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006.
3. Clarify the note added to the table in specification 15800, 2.02 C: 18-gauge stainless steel is acceptable for a grease duct but carbon steel shall be a minimum of 16-gauge. Reference: Section 506.3.1.1, IMC 2006.
12/31/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved