Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02912
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/21/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/31/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Make up air that is not heated (or cooled) may not be introduced into the kitchen in such a way that it reduces the comfort conditions of the occupied space. Show how the terminations of the ducts from MAU-1 and MAU-2 comply with the requirements of Section 508.1.1, IMC 2006. 2. Comment not resolved. If the make up air ducts are insulated, the insulation within 18" of the Type I hood shall be "… non-combustible or listed for the application." Show that the make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006. 3. Clarify the note added to the table in specification 15800, 2.02 C: 18-gauge stainless steel is acceptable for a grease duct but carbon steel shall be a minimum of 16-gauge. Reference: Section 506.3.1.1, IMC 2006. |
| 12/31/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |