Permit Number: T09CM02528
Parcel: 12510006B

Review Status: Active

Review Details: POST 3RD PARTY REVIEW

Permit Number - T09CM02528
Review Name: POST 3RD PARTY REVIEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2009 MARTIN BROWN FIRE REVIEW Approv-Cond Per General Note 30 (sheet A0.0), intent is to serve 2nd floor with 1 fire riser. Verify no area protected by 1 fire riser exceeds 52,000 square feet (NFPA 13 requirement).
10/29/2009 GERRY KOZIOL WWM REVIEW Approved
11/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/02/2009 ROBERT SHERRY WATER REVIEW Approved