Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T09CM02290
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/19/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | needs to build public sewer |
| 03/22/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Complete the energy analysis shown on sheet M2; i.e. show the design values for the opaque doors. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include the R-values of the insulation and the U-factors of the doors. Reference: Section 104.2, IECC 2006. |
| 03/22/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the reference site utility plan noted on sheet P1 that shows the location of the water meter, reduced pressure backflow preventer, the building sewer, and the rim elevation of the next upstream manhole. Reference: Section 103.2.3, UPC 2006. 2. A service sink is defined as having, as a minimum, a 2" trap and trap arm. Clarify the specifications for P3: if it has a 1-1/4" tailpiece, it cannot have a 2" trap and trap arm. Reference: Table 7-3 and Section 1003.3, UPC 2006. 3. Provide a design for mounting shelf for the water heater on the ceiling of the restroom along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. |
| 03/22/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A0.0; BUILDING CODE REVIEW CHECKLIST: THE TABLE FOR OCCUPANCY LOAD IS 1004.1.1. REVISE NOTE. 2. SHEET A0.0; BUILDING CODE REVIEW CHECKLIST: THE TABLE FOR EXITS IS 1005.1. REVISE NOTE. 3. SHEET A0.0; BUILDING CODE REVIEW CHECKLIST: THE TABLE FOR TRAVEL DISTANCE IS 1016.1. REVISE NOTE. 4. SHEET A2.0; INTERIOR PARTITIONS: PROVIDE BRACING AND DETAILS AT THE INTERIOR PARTITION WALLS TO RESIST THE REQUIRED LATERAL LOADS OF THE IBC SECTION 1607.13. 5. SHEET A4.0; DETAIL 3: THE SINK AND COUNTER AREA MUST MEET ACCESSIBILITY REQUIREMENTS OF THE IBC SECTION 1109.3. 6. SHEET A4.0; PLAN B: PROVIDE STRUCTURAL CALCULATIONS FOR THE ADEQUACY OF THE 6" CEILING FRAMING ABOVE THE RESTROOM TO SUPPORT THE WATER HEATER (INDICATED ON P1). 7. SHEET S2; FOUNDATION AND EARTHWORK GENERAL STRUCTURAL NOTES: THE SOILS ENGINEERING REPORT REFERENCED IN NOTE 1 WAS NOT PROVIDED FOR REVIEW. PLEASE SUBMIT. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/22/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Clarify the size of the water meter to be installed: 5/8" or 1"; Tucson Water does not provide a ¾" water meter. |
| 03/23/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 03/25/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/01/2010 | TERRY STEVENS | ZONING | REVIEW | Denied | 04/01/2010 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/09/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 04/09/2010 | DELMA ROBEY | REJECT SHELF | Completed |