Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T09CM02282
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006 2. Indirect waste receptors shall not be installed in a closet or cupboard. Reference: Section 804.1, UPC 2006. |
| 11/16/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/16/2009 | DROBEY1 | FIRE | REVIEW | Needs Review |