| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sinks, with an indirect connection for the sanitizing compartments only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. 2. The proposed FOG (Fats, Oils, and Greases) disposal systems are considered to be engineered systems. Provide the technical documentation and the manufacturer's installation instructions for the proposed FOG disposal systems. Show a detail (i.e. a riser diagram) showing how the FOG disposal systems are to be plumbed. Reference: Sections 103.2.3, 301.1.3, 301.2, and 1015.0, UPC 2006. |
| 04/11/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROVIDE CUT-SHEETS AND POWER REQUIREMENTS FOR HIGHLAND TANK GREASE TRAPS. REVISE ELECTRICAL PLAN SHEETS AS NECESSARY. |