Permit Number: T09CM02243
Parcel: 12512080A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02243
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/07/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans (M2) sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2006. Note: The non-sealed drawing M-2 appears to show the make up air being introduced into the area adjacent to each hood through 4-way ceiling diffusers which, depending upon their discharge velocities may adversely effect the hood operation and not comply with the hood manufacturer's installation instructions. Reference: Sections 304.1 and 304.2, IMC 2006.
05/24/2010 DAVE MANN FIRE REVIEW Approved
05/24/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 3360 E Speedway, Whole Foods,
T09CM02243

The electrical plans have been denied for the following:

1. Sheet E0.2, Shows Panel DPI with only the new loads, ( 43.1 amps) no Pnl A no B, it's also being fed from a 600 anp fuse, Corect pnael shcedule to show full schedule, and correct fuse at Main Switchboard.
2. Same for Panel DP2 as number .

Rat Majuta,PDSD, City of Tucson
Elect Pln Review
5/21/10
Ray.Majuta@tucsonaz.gov
05/24/2010 GBONILL1 WWM REVIEW Needs Review