| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/07/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans (M2) sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2006. Note: The non-sealed drawing M-2 appears to show the make up air being introduced into the area adjacent to each hood through 4-way ceiling diffusers which, depending upon their discharge velocities may adversely effect the hood operation and not comply with the hood manufacturer's installation instructions. Reference: Sections 304.1 and 304.2, IMC 2006. |
| 05/24/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/24/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 3360 E Speedway, Whole Foods, T09CM02243 The electrical plans have been denied for the following: 1. Sheet E0.2, Shows Panel DPI with only the new loads, ( 43.1 amps) no Pnl A no B, it's also being fed from a 600 anp fuse, Corect pnael shcedule to show full schedule, and correct fuse at Main Switchboard. 2. Same for Panel DP2 as number . Rat Majuta,PDSD, City of Tucson Elect Pln Review 5/21/10 Ray.Majuta@tucsonaz.gov |
| 05/24/2010 | GBONILL1 | WWM | REVIEW | Needs Review |