Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02243
Parcel: 12512080A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02243
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2010 GBONILL1 FIRE REVIEW Needs Review
04/16/2010 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/16/2010 GBONILL1 WWM REVIEW Needs Review
04/16/2010 LOREN MAKUS ENGINEERING REVIEW Approved
04/22/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide an automatic fuel shutoff valve for the gas-fired appliances located under each of the type I hoods. Reference: Section 904.3.3, IFC 2006.
04/23/2010 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide information to show that the operation of the Type I hoods and the hood exhaust fans comply with Section 507.2.1.1, IMC 2006.
3. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2006. Note: The non-sealed drawing M-2 appears to show the make up air being introduced into the area adjacent to each hood through 4-way ceiling diffusers which, depending upon their discharge velocities may adversely effect the hood operation and not comply with the hood manufacturer's installation instructions. Reference: Sections 304.1 and 304.2, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
05/07/2010 SUE REEVES REJECT SHELF Completed