Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02243
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/16/2010 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/16/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/16/2010 | GBONILL1 | WWM | REVIEW | Needs Review | |
04/16/2010 | GBONILL1 | FIRE | REVIEW | Needs Review | |
04/22/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide an automatic fuel shutoff valve for the gas-fired appliances located under each of the type I hoods. Reference: Section 904.3.3, IFC 2006. |
04/23/2010 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide information to show that the operation of the Type I hoods and the hood exhaust fans comply with Section 507.2.1.1, IMC 2006. 3. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2006. Note: The non-sealed drawing M-2 appears to show the make up air being introduced into the area adjacent to each hood through 4-way ceiling diffusers which, depending upon their discharge velocities may adversely effect the hood operation and not comply with the hood manufacturer's installation instructions. Reference: Sections 304.1 and 304.2, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/07/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
05/07/2010 | SUE REEVES | REJECT SHELF | Completed |