Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02243
Parcel: 12512080A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02243
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2010 GBONILL1 WWM REVIEW Needs Review
08/21/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
08/21/2009 ERIC NEWCOMB ADA REVIEW Passed
08/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE CODE ANALYSIS FOR OCCUPANCY LOAD, BUILDING TYPE, ETC.
08/21/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
08/21/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/25/2009 ROBERT SHERRY WATER REVIEW Approved
08/25/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 3360 E Speedway Bl, T09CM02243
Kitchen Equipment.

The Electrical Plans have been denied for the following;

Provide Engineered drawings for electrical work as per 2005 NEC.


Ray T Majuta
PDS City of Tucson
Elect Plan Ck
8/25/09
520-837-4988
Ray.Majuta@tucsonaz.gov
08/25/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the listing information for the new exhaust fans and the make up air units.
2. Show that the outlet of fan EF-1 complies with the requirements of Section 506.5.5, IMC 2006.
3. Provide balancing information for the new Type I and Type II hoods. Reference: Sections 507.1 and 507.13, IMC 2006.
4. Provide information to show that the operation of the Type I hoods and the hood exhaust fans comply with Section 507.2.1.1, IMC 2006.
5. Revise the installation of the hood to provide 18" of clearance between the hood and combustible construction (note that wood studs covered by gypsum board and a sheet of stainless steel are considered combustible construction by the IMC). Reference: Section 507.9, IMC 2006.
6. Show that the roof top air-conditioning units supplying make up air for the kitchen hood are electrically interlocked to the exhaust fans. Reference: Section 508.1, IMC 2006.
7. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2006.
08/25/2009 DAVE MANN FIRE REVIEW Denied Please provide code review checklist. Exiting does not appear to meet IFC Chap 10.
08/25/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a plumbing plan showing how the new trench drains fit into the existing plumbing system.
11/02/2009 LOREN MAKUS ENGINEERING REVIEW Approved