Permit Number: T09CM02230
Parcel: 99999999Z

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM02230
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/13/2009 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Denied Project : 10428 E Mary Ann Cleveland Wy
T09CM02230
Booster Station

The Electrical plans have been denied for the following:

1. Provide information on the VFD 4 PUMP CONTROLLER,
fault current capability, overcurrent protection provided for pumps, voltage and amperage,nema rating, please this information on plan.
2. Provide the size of the junction box to be used as required by NEC 2005 for Note F as stated on Sheet 6.
3. Note all inspections on this project to be made by our department unless approved for others to make by our Department"s Building Official.

Ray T Majuta
Elect Pln Ck, DPSD< City of Tucson
11/17/
Ray.Majuta@tucsonaz.gov
11/13/2009 JASON GREEN ENGINEERING REVIEW Approved
11/13/2009 ENEWCOM1 WATER REVIEW Passed
11/13/2009 MARTIN BROWN FIRE REVIEW Approved
11/13/2009 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
11/13/2009 TERRY STEVENS ZONING REVIEW Passed