Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM02230
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/13/2009 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project : 10428 E Mary Ann Cleveland Wy T09CM02230 Booster Station The Electrical plans have been denied for the following: 1. Provide information on the VFD 4 PUMP CONTROLLER, fault current capability, overcurrent protection provided for pumps, voltage and amperage,nema rating, please this information on plan. 2. Provide the size of the junction box to be used as required by NEC 2005 for Note F as stated on Sheet 6. 3. Note all inspections on this project to be made by our department unless approved for others to make by our Department"s Building Official. Ray T Majuta Elect Pln Ck, DPSD< City of Tucson 11/17/ Ray.Majuta@tucsonaz.gov |
| 11/13/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/13/2009 | ENEWCOM1 | WATER | REVIEW | Passed | |
| 11/13/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/13/2009 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/13/2009 | TERRY STEVENS | ZONING | REVIEW | Passed |