Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE
Permit Number - T09CM02186
Review Name: RESUBMITTAL - SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | For the building structure submittal, please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
| 11/17/2009 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. At the marked crossing in from of the existing loading zone: a. If zoning allows this location which I don't believe they will (reference zoning comments), reconfigure the detectable warnings to be in direction of travel. Turn the one at the bottom of the sidewal;k ramp 90 degrees, provide another one just prior to crossing the drop off zone, maintain the concrete walk flush and retain a 6" high curb for separation. 2. For all the curb ramps with landscaping on either side, it is suggested to delete the flared concrete sides and have a simple curb return ramp. (at 4 locations). END OF REVIEW |
| 11/19/2009 | JASON GREEN | ENGINEERING | REVIEW | Needs Review | |
| 11/19/2009 | DROBEY1 | LANDSCAPE | REVIEW | Needs Review | |
| 11/19/2009 | DROBEY1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/19/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |