Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02053
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2009 DAVE MANN FIRE REVIEW Approved
09/17/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
09/17/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide energy code compliance calculations (Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2003 or an appeal to the building official may be submitted to limit the occupancy of the building to 193 people. Reference: Section 403.3, IMC 2006.
09/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (the west floor sink). Reference: Section 707.4, UPC 2006.
2. Comment not addressed. Provide roof drainage calculations and plans. All roof areas shall be drained by roof drains, scuppers, or gutters. Reference: Section 1101.11.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2009 CPIERCE1 OUT TO CUSTOMER Completed
09/22/2009 SUE REEVES REJECT SHELF Completed