Permit Number: T09CM02007
Parcel: 12705078A

Address:
1070 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02007
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2009 MARTIN BROWN FIRE REVIEW Approved
07/30/2009 GERRY KOZIOL WWM REVIEW Denied NEED INDUSTRIAL WASTEWATER CONTROL (IWC) REVIEW & APPROVAL FOR GREASE INTERCEPTOR- TOM TOMCHAK 443-6200 5025 W INA RD
08/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/05/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
08/10/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/11/2009 ROBERT SHERRY WATER REVIEW Approved
08/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the source of power for the existing water heater. It is called out as gas-fired on the architectural and electrical sheets but no gas appears to be serving it. If it is supplied with gas from the new gas meter, include it on the drawings. Reference: Section 103.2.3, UPC 2006.
2. Clarify the existence of the soda dispenser called out on the plumbing kitchen schedule (but nowhere else). Reference: Section 103.2.3, UPC 2006.
3. Provide the sizes for the branch gas pipes serving the cooking equipment under the hood. Reference: Section 103.2.3, UPC 2006.
4. Is a grease interceptor existing or required for this restaurant by Pima County Industrial Waste Control. Reference: Section 1014.1, UPC 2006.
08/19/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2009 DELMA ROBEY OUT TO CUSTOMER Completed
09/14/2009 SUE REEVES REJECT SHELF Completed