Permit Number: T09CM01970
Parcel: 13101054A

Address:
4702 E 22ND ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM01970
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revisions to sheet P1 are inconsistant with regard to the size of the water pipes and the reduction of the water service to the building will result in water velocities greater than 8 feet per second. In addition, the pipe sizing is not supported by the calculations shown on sheet P2.