Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM01970
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The revisions to sheet P1 are inconsistant with regard to the size of the water pipes and the reduction of the water service to the building will result in water velocities greater than 8 feet per second. In addition, the pipe sizing is not supported by the calculations shown on sheet P2. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/02/2010 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 06/02/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |