The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09CM01970
Parcel: 13101054A

Address:
4702 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM01970
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2009 DAVE MANN FIRE REVIEW Approved
10/19/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: October 19 2009
SUBJECT: Capin Car Wash - Site Plan
TO: Eric Fletcher
LOCATION: 4702 E 22nd Street, T14S, R14E, Section 23, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09CM01970 (2nd Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the site plan with the next submittal.

Site Plan:

Comment 6 to remain until DSMR have been reviewed. If DSMR is approve provide number on plans along with all other associated plan review numbers.

6. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Indicate curb returns for MS&R and call out radius on plans. Curb returns are required for driveways along MS&R's, please depict and label 25-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along 22nd Street and Swan Road or provide letter or email from Transportation indicating that curb returns are not required. For letter or email to address Transportation Management Guideline requirements, please contact Jose Ortiz, Civil Engineer 520-837-6730 or jose.ortiz@tucsonaz.gov .

11. Provide base flood elevation along with the regulatory elevation on site plan and include datum.
Verify that water surface elevations and cross sections match the hydrology report.

Additional Comment: Drainage statement does not appear to match the Hydrology Report. Please clarify or revise accordingly.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
10/23/2009 ANDREW CONNOR LANDSCAPE REVIEW Approved Ensure that all Engineering & Zoning comments and concerns are addressed prior to landscape approval stamp

The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.
11/04/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Capin - 22nd & Swan
T09CM01970
Site Plan (2nd Review)

TRANSMITTAL DATE: November 4, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. The DSMR must be approved prior to approval of the site plan. If the DSMR is approved, on the site plan provide: the DSMR Number, Date of Approval, What was approved, and any Conditions for Approval. Once the required information is provided on the plan Zoning is willing to provide an over-the-counter review. Please call or email to schedule and appointment for this review. D.S. 2-02.2.1.A.12 Per D.S 3-05.2.2.B.1 A minimum setback distance of five (5) feet for a pedestrian refuge area must be maintained between any enclosed structure and a parking area access lane (PAAL) and D.S. 2-08.4.1.B A sidewalk will be provided adjacent and parallel to any PAAL on the side where buildings are located. This said provide the required 5'-0" pedestrian refuge and sidewalk along the southern most PAAL and the structure located on the adjacent property.

3. D.S. 2-02.2.1.A.In regards to the Billboard that is shown as to be removed from the site, at a very minimum the building certificated of occupancy will be held until the Billboard is removed from site. Staff is currently in discussions with the Director in regards to this issue.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm01970

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
11/05/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/05/2009 RONALD BROWN ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2009 CPIERCE1 OUT TO CUSTOMER Completed
11/06/2009 SUE REEVES REJECT SHELF Completed