Permit Number: T09CM01843
Parcel: 133224970

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01843
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied RESUBMITTAL COMMENTS
1. Minimum size lettering font is 3/32". upper and lower case. Please resize all lettering that are less than 3/32 and reprint sheets.
RESPONSE COMMENT: Sheets T1.0, A1.1, A1.B, A1.C, A1.D, A1.E, A1.F, E1.0 AND E2.0 all have lettering less than 3/32".
2. OK
3. Please provide completed Special Inspection Certificates for all special inspections as outlined on sheet S1.1.
RESPONSE COMMENT: Incomplete Certificate attached. Please fill in selected special inspectors for the special inspections required, provide the registrant seal and signature and submit for DSD approval.
4. OK
5. OK
6. OK

STRUCTURAL REVIEW BY ERIC NEWCOMB

7. OK
8. OK
9. OK
10. OK
11. OK
12. OK
13. OK

END OF REVIEW
01/08/2010 DAVID RIVERA ZONING REVIEW Approved
01/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/12/2010 ROBERT SHERRY WATER REVIEW Approved
01/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise General Note: the roof drain sizing shall be based on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour, not 2" per hour. (The roof drain sizing on the plans is correct.) Reference: Section 1101.11.1 and Table D-1, UPC 2006.
2. Correct the water piping shown inside the building on the plumbing floor plan: it appears to be labeled as natural gas piping. Reference: Section 103.2.3, UPC 2006.
(The preceding comments can be resolved over the counter.)
01/25/2010 GERRY KOZIOL WWM REVIEW Approved
02/01/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
02/02/2010 SUE REEVES REJECT SHELF Completed