Permit Number: T09CM01843
Parcel: 133224970

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T09CM01843
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the Site Plan Detail Utility Sheet (5 of 6, sealed 10/27/09) to agree with the Grading and Improvement Plan, Private Utility Sheet (5 of 7, sealed 01/04/10).
2. Backflow protection is not required for the fire water service. Reference: Section 603.4.16, UPC 2006, as amended by the City of Tucson and ARS 41-2168.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
02/02/2010 SUE REEVES REJECT SHELF Completed