Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T09CM01842
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/05/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/06/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM01842--------3146 E Grant Rd The plumbing plan shows a water heater which is 120 volt 3 kv at 25 amps on a one pole cb, the electrical shows a 2 pole cb, 30 amp. Please clairfy which one it will be. Ray T Majuta Elect pln Ck PDSD City of Tuc 11/07/09 Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/10/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
11/10/2009 | SUE REEVES | REJECT SHELF | Completed |