Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01842
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/20/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. SHEET 1.1; FLOOR PLAN: ELEVATIONS 2 AND 3 IN THE TOILET ROOM REFERENCED ON THE PLAN ARE SHOWN AS ELEVATIONS 4 AND 5. CLARIFY. 2. SHEET 1.1; DOOR TYPES ELEVATION: THE SECTION CUT THROUGH THE GARAGE HEADER REFERENCED AS 84/1.1 IS INCORRECT. CLARIFY. |
| 07/20/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 07/21/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | July 21, 2009 FLOODPLAIN USE PERMIT # T09OT01459 PROJECT ADDRESS: 3146 E Grant Road APPLICANT'S NAME: AZ Auto Spa PROPERTY OWNER: Oscar Diaz This parcel lies in a City of Tucson identified 100-year floodplain. The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as: PARCEL 122-15-161A; 3146 E Grant Road, Tucson, AZ 85716, PALO VERDE AMENDED E100' W180' S140' N165' LOT 2 BLK 1. In a portion of Township 14 South, Range 14 East, Section 4, for s tenant improvement to an existing non-conforming structure. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard Area Regulations, and are bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require application for, review and approval of an additional Floodplain Use Permit. This floodplain use permit is issued with the following conditions: 1) If improvements equal or exceed 50% of the current value of the structure; no other improvements will be permitted unless the entire structure is brought into compliance with the City of Tucson Floodplain and Erosion Hazard Area Regulations (Chapter 26, Tucson Code). If the project is determined to be a substantial improvement, and, if it is determined that the lowest flood elevation is below the regulatory floor elevation, a design submittal, and review and acceptance of the submittal for floodproofing will be required and shall conform to current City of Tucson and FEMA floodplain development requirements in effect on the date of authorization by the Development Services Department. 2) The proposed improvements shall not impose conditions that would increase the flood damage potential to the combined proposed and existing building, by 50 percent or greater of the existing structure's value. 3) Per cost estimate provided by Bonmar Construction, Richard Spreyser, Owner and Mario Coelho, Supervisor (Dated 7/21/09) estimate of ($11,400.00) was provided showing that the improvements are less than 50 % (estimate was 19%) of the assessed value of the structure per the Pima County Assessor Property Inquiry (2009) (valuation excluding land value, by taking 70% of the total value - $61,015.00). No person shall repair or alter property in a piecemeal manner so as to avoid the provisions of Section 26-4.1.a.3, Chapter 26-Tucson Code. The estimate will be recorded and any future improvements will be added to it. 4) This project is located within a City of Tucson (100-year) floodplain. 5) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties. 6) This Floodplain Use Permit is issues concurrently with the improvement plans/permit. Copies of these documents shall be kept in a readily accessible location on site at all times. 7) Any future permanent, freestanding walls or other structures shall have separate floodplain use permit applications submitted to this office for review and approval. 8) An application/processing fee of $50.00 (submittal fee) must accompany each future request for work to be authorized under this floodplain use permit. Engineering study review fees of $150.00 may be imposed based upon the fee schedule in the current floodplain ordinance. 9) The associated improvements are with permit activity number T09CM01842. 10) The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be done to the existing building, and that all addition, improvements or repairs to the building are included in the construction plans and/or documents herewith. No other improvements, repairs, reconstruction, additions or remodeling have been made to the structure that is not indicated in the attached plans and/or documents. 11) Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department Engineering Division. This permit may be renewed for up to one year, in the absence of Registered Plant authorization, at the sole discretion of the City Engineer or designated representatives. 12) This permit is specific to the improvements for 3146 E Grant Rd, as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit. This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit. APPLICANT NAME: AZ Auto Spa ADDRESS: 3146 E. Grant Road, Tucson AZ 85716 PHONE: 520-850-1640 OWNER: Oscar Diaz ADDRESS: 2718 N Fairoaks Ave, Tucson, AZ 85712 PHONE: (EXPIRATION DATE) Month: 7 Day: 21 Year: 2010 SIGNATURE OF APPLICANT DATE The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions. |
| 07/22/2009 | SREEVES1 | WWM | REVIEW | Approved | |
| 07/28/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The plans have been reviewed to the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. 2. Provide plumbing plans to a known scale. Reference: Section 103.2.3, UPC 2006. 3. Clarify how the existing grease interceptor will be taken out of service. Reference: Sections 103.2.3 and 1014.3.7, UPC 2006. 4. The specified drinking fountain (Elkay EZS8) does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. |
| 07/28/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/28/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. Reference: Section 106.1.1, IBC 2006. 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 3. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006. 4. Revise the sequence of operation for the restroom exhaust to prevent recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. |
| 08/04/2009 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Affordable Auto Tint & Detail T09CM01842 Building Plan (1st Review) TRANSMITTAL DATE: August 4, 2009 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. A Special Exception Approval for the proposed use must be approved prior to approval of this plan. If the Special Exception is approved provide the following information on the plan; Special Exception number, date of approval, conditions of approval. 3. Zoning will re-review the building plan on the next submittal to insure compliance Special Exception. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t09cm01842.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
| 08/12/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 3146 E Grant Rd, T09CM1842 Car Repair The Electrical plans for this permit have been denied for the following; 1. These plans do not mention 2005 NEC 511, the restrictions for wiring in these locations. Commercial Garages,Repair and Storage. Indicate classified locations, describe receptacles,lighting, wiring to be used in these area as per 2005 NEC 511. If any area is to be un-classified indicate why. Ray T Majuta PDS City of Tucson Electrical Plan Check 8/17/09 Ray.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 08/31/2009 | SUE REEVES | REJECT SHELF | Completed |