Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01648
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/30/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/01/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/02/2009 | RICK HOLLANDER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project: T09CM01647 245 E. Congress St TI Electrical plans have been denied for the following: E1: 1) Circuit conductor sizes needed 2) Show circuit wiring for connections 3) Show calculations on page for IECC Lighting 4) Need light for servicing at A/C 210.70(C) 5) Need 125% load demand calculated into lighting circuits 220.12, 220.43 E2: Needed for power plan (on K2) 1) See notes 1&2 E1 2) Receptacle desigantion on kitchen schedule not as per code size for circuit 3) Kitchen receptacles to be GFCI protected 210.8 and define kitchen area 4) Note for listing and labeling 5) Show A/C & F/C on plans with circuits E100: 1) Verify A/C motor loads 220.50 2) Need existing & new loads for service 3) Calculate kitchen equipment 220.56 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/04/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |