Permit Number: T09CM01648
Parcel: 11706183B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01648
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/02/2009 RICK HOLLANDER ELECTRICAL-COMMERCIAL REVIEW Approved Project: T09CM01647
245 E. Congress St
TI



Electrical plans have been denied for the following:

E1:
1) Circuit conductor sizes needed
2) Show circuit wiring for connections
3) Show calculations on page for IECC Lighting
4) Need light for servicing at A/C 210.70(C)
5) Need 125% load demand calculated into lighting circuits 220.12, 220.43

E2: Needed for power plan (on K2)
1) See notes 1&2 E1
2) Receptacle desigantion on kitchen schedule not as per code size for circuit
3) Kitchen receptacles to be GFCI protected 210.8 and define kitchen area
4) Note for listing and labeling
5) Show A/C & F/C on plans with circuits

E100:
1) Verify A/C motor loads 220.50
2) Need existing & new loads for service
3) Calculate kitchen equipment 220.56

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2009 DELMA ROBEY OUT TO CUSTOMER Completed