Permit Number: T09CM01648
Parcel: 11706183B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01648
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2009 DAVID RIVERA ZONING REVIEW Approved
06/29/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/29/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
06/29/2009 ROBERT SHERRY WATER REVIEW Approved
06/29/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need structural calculations for fan coil unit
2. Need structural details and calculations for water heater support from structure
06/29/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications for the water heater, the floor drains, and the sinks.
2. Provide a vent for each trap.
3. Show how the temperature of the hot water to the lavatory will be limited to 110 degrees Fahrenheit or less.
4. Provide for thermal expansion of the hot water.
5. Show the size, route and termination of the temperature and pressure relief for the water heater.
6. Provide a drain pan with drain for the water heater.
7. Show how the trap primer is to be installed.
8. Specify the backflow devices to be installed for the appliances directly connected to domestic water.
06/29/2009 DAVE MANN FIRE REVIEW Approved
06/29/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
06/29/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
06/30/2009 GERRY KOZIOL WWM REVIEW Approved
06/30/2009 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review Electrical Plans incomplete----
Ray T Majuta
DSD Elecxtrical Plan Ck
6/29/09
06/30/2009 PAUL MACHADO ENGINEERING REVIEW Approved