Permit Number: T09CM01573
Parcel: 11450001A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T09CM01573
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/06/2009 SEPTIC APPROVAL WWM REVIEW Denied need to permit septic system (exsisting septic expired)
08/06/2009 DAVE MANN FIRE REVIEW Approved
08/06/2009 ROBERT SHERRY WATER REVIEW Denied Clarify the source of water for this building. The pressure loss calculations imply that Tucson Water is the source ("75PSI…verified with Tucson Water Co.") but the calculations do not include pressure drops for either a water meter or a backflow preventer. The plumbing plan refers to the site plan for continuation of the 1-1/2" water service line but no domestic water lines are shown on the site plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
08/11/2009 SUE REEVES REJECT SHELF Completed