Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2009 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 10/15/2009,

Drainage Report:

1. According to Section 8.4. of the Drainage Manual, "No Building shall be built within the erosion-hazard setback limit associated with the main channel, unless adequate bank protection is first installed". The structure is shown with the erosion setback line of the onsite tributary to the Pantano Wash. Show the proposed structure outside all erosion-hazard limits or check if the erosion hazard setback location is accurate. If the wash bank is not clearly defined, the erosion setback line can be taken from the 10-year floodplain limit.
5. If the corral is proposed to be constructed with the new residence, it shall be shown on the drainage exhibit. The corral can be elevated a minimum of 1' in sheet flow areas or It can be constructed with collapsible fence. In case of a flood, the walls collapse and flow can continue without obstruction.

Site Plan:

1. Provide the 100-year water surface elevations for all floodplains that may impact the proposed structure as required by D.S. 2-02.1.15. Additionally, show the erosion hazard setback line for the onsite Pantano Wash tributary. The proposed structure shall be outside the erosion hazard setback line.
2. Provide the proposed finish grades around the proposed improvements as required by D.S. 2-02.1.16.
3. Since Nebraska is a public right of way, label it as such, dimension it and show the street center line (D.S. 2-02.2.1.19). Additionally, since the street width is substandard, show an additional 10.5' setback from the lot line inwards, to allow future street widening. The proposed structure shall be located outside all setbacks.
4. Show existing and future sight visibility triangles at the parcel entrances (D.S. 2-02.2.1.10).
5. Show all easements of record, if applicable, as required by D.S. 2-02.1.20.
6. The Site Plan needs to be stamped by a registered civil engineer.
7. Clarify how the cut/fill slopes will be treated and or stabilized. Provide a geotechnical report addressing slope treatment/stabilization.


Resubmittal Required: Revised Site Plan and Drainage Report
10/15/2009 ANDREW CONNOR NPPO REVIEW Denied A Native Plant Preservation plan is required. If the set-aside methodology is used, the mitigation requirement is for a minimum of thirty (30) percent of the site to be set aside in perpetuity as NUOS area. The area to be set aside is required to be be delineated and legally described on the site plan (with recording data included) and legally protected by a document, such as a conservation easement (Exhibit C), recorded by the County Recorder.

The set-aside method typically requires an Environmental Resource Report that identifies the areas of the site with highest natural resource value. In this case the area identified on the TDOT Map as "Critical and Sensitive Biological Communities" would be an acceptable delineation.
10/22/2009 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T09CM01368
11221 East Nebraska Road
New SFR
3rd zoning review


TRANSMITTAL: October 23, 2009


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1) This review is for a new single-family residence (SFR) in the SR Zone (LUC Section 2.2.4.2.A.1). Provide the correct zoning on the plot plan, in the site data information and on all the adjacent lots. The Development Designator is "C" (LUC Section 3.2.3.1.A) and the Perimeter Yard Indicator is BB (LUC Section 3.2.6.4). This site is subject to LUC Section 3.5.7.1.F.

2) Parcels 205-66-099C and 205-66-099D have been combined on September 9, 2009 to Parcel 205-66-099F.

3) Access has been confirmed by Jose Ortiz, e-mail September 8th 2009.

4) There appears to be a SFR on the site according to the records with the Pima County Assessor and the aerial photos. The maximum number of units in the SR Zone is one (1) (LUC Sections 2.2.4.2.A.1 and 3.2.3.1.A). Provide a demo permit for the existing SFR.

5) The property lines on the plot plan are incomplete. Provide the correct property lines with dimensions on the plot plan. Also place dimension of the proposed structure and any existing structures to remain from the nearest edge of each structure to each property line (LUC Section 3.2.6.4).

6) Completed.

7) Completed.