Permit Number - T09CM01366
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2009 RONALD BROWN ADA REVIEW Passed ADAAG NOT REQUIRED
06/01/2009 DAVE MANN FIRE REVIEW Approved
06/08/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.0; DETAIL 101: 10'-10" TALL MASONRY WALL REQUIRES STRUCTURAL CALCULATIONS FOR THE WALL AND THE FOOTING PER IBC 105.2.
06/09/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
06/10/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/18/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM01366 , TAA
7280 S Tucson Bl
Public Parking Electrial Retro-fit

The electrical plans have been denied for the following;

1.Sheet E1.0 , Key Note 2 shows only 3-3/0's per phase, should be 4 , include the neutral.
2. Sheet E2.0, will the new 450kwa Generator require it's own ground system, or will new 600 Amp ATS provide a solidly connected neutral, the Spec book does not indicate.
3. New electrical equipment is being introduced, please provide a fault current calculation for service and panels, cannot find any information on existing.
4. The 400 Amp disconnect which feeds panels LER and LNR provides only 150 Amps, please provide the load calculation for Panel LER.



Ray T Majuta
Elect Plan CK, DSD City of Tucson
6/21/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2009 CPIERCE1 OUT TO CUSTOMER Completed
06/29/2009 SUE REEVES REJECT SHELF Completed