Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
7280 S TUCSON BL
Address NEW:
7280 S TUCSON BL
Apply Date:
05/29/2009
Applicant:
N/A
Description:
REPLACE: GENERATOR
Contractors:
  • WILSON ELECTRIC SERVICES CORP

Permit Reviews

Permit Number - T09CM01366
Permit Status: Final
Permit Description: REPLACE: GENERATOR
Start Date Submittal Complete Date Status  
05/29/2009 PLANS OK TO SUBMIT - COMM 05/29/2009 COMPLETED Review Details
05/29/2009 COMMERCIAL-BLDG/FIRE/ZONING/ENG 06/29/2009 COMPLETED Review Details
06/30/2009 RESUBMITTAL 10/27/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T09CM01366
Permit Status: Final
Permit Description: REPLACE: GENERATOR
Total Outstanding Activity Conditions - 1
Date Name
05/29/2009 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T09CM01366
Permit Description: REPLACE: GENERATOR
Total Completed Inspections - 14
Date Description Inspector Results Comments
11/19/2009 ELECTRIC - INTERMEDIATE RHOLLAND Approved 1) OK CHANGE TO 200 AMP DISCONNECT
2) RE-FED OF 60 AMP DISCONNECT AND WIRING
3) RECEIVED CHECK #1432 $150.00
11/19/2009 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
12/17/2009 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
1) OK CONDUITS UNDER SLAB
12/28/2009 EXCAVATION/LAYOUT REBAR & ZON MHENSON Approved IVRS - Inspection :*
1) SCHNEIDER SPECIAL INSPECTED
12/28/2009 ELECTRIC - UFER RHOLLAND Approved IVRS - Inspection :*
1) OK 20' IN TRENCH, TO REBAR AND #2 CU
2) OK 2 GROUND RODS AND #2 CU
12/28/2009 ELECTRIC - PROGRESS RHOLLAND Approved IVRS - Inspection :*
01/14/2010 REINFORCED MASONRY PRE-GROUT GDABBS Approved IVRS - Inspection :*
1) TOP OUT OF CMU WALLS
02/17/2010 TEP CLEARANCE - AM JWEATHER Approved ECO CLEARED PER R. HOLLANDER
03/19/2010 BUILDING - FINAL RHOLLAND Approved IVRS - Inspection :*
03/19/2010 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
03/19/2010 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :*
03/19/2010 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection :*
03/19/2010 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
03/22/2010 PERMIT FINALED JWEATHER Approved