Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM01366
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2009 | RONALD BROWN | ADA | REVIEW | Passed | ADAAG NOT REQUIRED |
| 06/01/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/08/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S1.0; DETAIL 101: 10'-10" TALL MASONRY WALL REQUIRES STRUCTURAL CALCULATIONS FOR THE WALL AND THE FOOTING PER IBC 105.2. |
| 06/09/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Passed | |
| 06/10/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/18/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM01366 , TAA 7280 S Tucson Bl Public Parking Electrial Retro-fit The electrical plans have been denied for the following; 1.Sheet E1.0 , Key Note 2 shows only 3-3/0's per phase, should be 4 , include the neutral. 2. Sheet E2.0, will the new 450kwa Generator require it's own ground system, or will new 600 Amp ATS provide a solidly connected neutral, the Spec book does not indicate. 3. New electrical equipment is being introduced, please provide a fault current calculation for service and panels, cannot find any information on existing. 4. The 400 Amp disconnect which feeds panels LER and LNR provides only 150 Amps, please provide the load calculation for Panel LER. Ray T Majuta Elect Plan CK, DSD City of Tucson 6/21/09 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/29/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/29/2009 | SUE REEVES | REJECT SHELF | Completed |