Permit Number - T09CM00308
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Correct the size of the condensate drains as shown in detail 3/M3.2; the minimum condensate size is ¾". Refer to Section 307.2.2, IMC 2006, as amended by the City of Tucson and correct the condensate drains for the AC units as needed. |
| 04/22/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The gas pipe branches serving AC-1, AC-4, and AC-5 are too small based on Table 402.4(1), IFGC 2006 and the pipe lengths shown on sheet P7.1. The sizes of the gas pipes also vary between the details. |