The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09CM00284
Parcel: 126031030

Address:
4501 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00284
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2009 DAVID RIVERA ZONING REVIEW Approved
02/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Section 403.2.1 (3), IMC 2006
02/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/05/2009 ROBERT SHERRY WATER REVIEW Approved
02/05/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied REFERENCE H/C COMMENTS
02/05/2009 JASON GREEN ENGINEERING REVIEW Approved
02/05/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide an appeal to the building official to use the IPC.
02/05/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. GOVERNING ACCESSIBILITY CODE IS 2006 IBC, CHAPTER 11 AND ICC ANSI 117.1 2003 EDITION. CHANGE ALL ACCESSIBILITY REFERENCE TO ICC ANSI 117.1 NOT ADA
2. NEITHER TOILET MEETS ACCESSIBILITY REQUIREMENTS. THE BIG ONE DOES NOT HAVE PROPER TURN AROUND CLEARANCE. THE SMALLER ONE NEEDS A BUILDING OFFICAL APPEAL
3. EXIT DOOR JAMP CLEARANCE NOT IN COMPLIANCE WITH ANSI 404.3.2.1.
4. BOTTOM STAIR RISER NOT IN CODE COMPLIANCE, SECTION 1009.3.2, 4" MIN.
5. NOT ENOUGH DOOR CLEARANCE ACCESS TO BIG TOILET, EWCs TOO CLOSE TO DOOR. SUGGEST USING A POINT OF USE WATER DESPENSER.
02/05/2009 RONALD BROWN ADA REVIEW Passed not a city project
02/10/2009 CAGUILA1 WWM REVIEW Needs Review
02/10/2009 CAGUILA1 FIRE REVIEW Needs Review
02/10/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review