Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM00065
Parcel: 12217365A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM00065
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2009 DAVE MANN FIRE REVIEW Approved
01/12/2009 GERRY KOZIOL WWM REVIEW Approved
01/12/2009 RONALD BROWN ADA REVIEW Passed NOT A COT PROJECT
01/12/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
01/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide complete plumbing plans for the new work, including water pressure calculations, water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
2. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.
3. Provide equipment data for the water heater. Reference: Section 103.2.3, UPC 2006.
4. Provide information to show that the shower and tub/shower control valves conform to the requirements of ASSE 1016. Reference: Section 418.0, UPC 2006.
5. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference: Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2006.
6. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2. Include all fixtures (e.g. the dishwashers) when calculating the total demand. Reference: Section 610.3, UPC 2006.
7. Provide calculations showing how the water supply piping has been sized. If PEX tubing is to be used, provide the manufacturer's sizing data. Reference: Sections 610.4 and 610.5, UPC 2006.
8. Provide a schedule of waste fixture units for all plumbing fixtures using the values shown in table 7-3, UPC 2006. Reference: Section 703.1, UPC 2006.
9. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
10. Provide cleanouts sized per Section 707.11, UPC 2006.
11. Any fitting or connection in a drainage system that results in a reduction of the pipe area (i.e. 3" building sewer downstream of a 4" 2-way cleanout) is prohibited. Reference: Section 316.4.1, UPC 2006.
12. If a field inspection shows that the first floor elevation of the new building is less than 12" above the rim elevation of the next upstream manhole and a backwater valve (not a backflow prevention valve) is needed, refer to Section 904, UPC 2006, for venting requirements.
13. Provide the total number of drainage fixture units that are to be connected to the existing 4" HCS. If the total flow for the private sewage collection system for this project is in excess of 3000 gallons per day, the design for the system must be submitted to the Pima County Department of Environmental Quality for their approval prior to obtaining a permit for constructing the sewage collection system from the City of Tucson. Reference: A.R.S. 49-104 (B) (13).
14. Provide specifications and details to show how the fire-rating will be preserved at the combustible piping penetrations of the fire-resistance-rated partitions. Reference: Section 1505.0, UPC 2006.
01/14/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
01/14/2009 ROBERT SHERRY WATER REVIEW Denied 1. Confirm the availability of a 2-1/2" water meter. Provide the total connected water demand for the meter that will result from the addition of this building. Reference: Sections 610.1 and 610.2, UPC 2006.
2. The water supply to all new multi-family residential buildings shall be individually metered for each dwelling unit. The metering may be private or utility installed. If private meters are selected, the Tucson Water meter shall have a reduced pressure backflow preventer installed immediately downstream of the Tucson Water meter.
01/14/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 14 JANUARY 2009
T09M00065/TMM AND THE ANGEL CAMPUS ADDITIONS
REVIEWED BY RON BROWN

COMMERICAL REVIEW
2006 IBC

DENIED: SEE COMMENTS BELOW

I. SHEET CVR:
A. ALL DEFERRED SUBMITTALS MUST HAVE A LETTER OF INTENTION SENT TO THE BUILDING OFFICIAL, MR. JESSIE SANDERS. CONTACT CLAUDIA BUFORD (502) 837-4904 FOR PROCEDURES, FORMAT AND FEE STRUCTURE.
B. PROVIDE DETAILED CODE SEARCH ANALYSIS ON THIS SHEET.
II. SHEET SD-1 AND SD-2:
A. REFERENCE SITE H/C COMMENTS
III. SHEET A1:
A. GENERAL NOTE: AS PER 2006 IBC, SECTION 1107.6.2.12; ALL UNITS TO BE TYPE "B".
B. LEGEND: BECAUSE STRUCTURE IS SPRINKLERED, THE FIRE PARTITION NEED BE ONLY ½ HOUR [SECTIONS 708.1.2 AND 708.2 (2)] AND THE DOORS NEED BE ONLY 2O RATED, TABLE 715.4.
C. PLEASE PROVIDE PLUMBING AND ELECTRICAL PENETRATION FIRE SEAL DETAILS FOR ALL ELECTRICAL AND PLUMBING UTILITY PENETRATIONS THROUGH FIRE PARTITIONS. FIRE SEALANT PENETRATION ASSEMBLIES FOR ABS 2" AND LARGER IS HARD TO FIND. YOU MAY WANT TO RECONSIDER THE USE OF ABS PIPING.
D. PLEASE SHOW AND DENOTE ALL FIRE BLOCKING REQUIRED BY 2006 IBC.
IV. SHEET A3:
A. ROOF PLAN: SHOW HVAC ROOF MOUNTING DETAILS.
V. SHEET S-2:
A. FOR ALL NOTES DEFERRING ROOF TRUSS SUBMITTALS: ALL DEFERRED SUBMITTALS MUST HAVE A LETTER OF INTENTION SENT TO THE BUILDING OFFICIAL, MR. JESSIE SANDERS. CONTACT CLAUDIA BUFORD (502) 837-4904 FOR PROCEDURES, FORMAT AND FEE STRUCTURE.
B. SHOW LOCATION AND FRAMING DETAILS FOR ALL ROOF MOUNTED MECHANICAL UNITS ON ROOF. PROVIDE STRUCTURAL CALCULATIONS.

STRUCTURAL PLAN REVIEW
1. SHEET S-1; FOUNDATION PLAN: PROVIDE CALCULATIONS FOR FOUNDATION DESIGN.
2. SHEET S-1; SECTION 10/D-1: PROVIDE NOTE ON SECTION THAT OPTIONAL FOOTINGS (SIMILAR TO SECTIONS 1, 2, & 3) MAY BE USED AT THIS FOOTING.
3. SHEET S-2; ROOF FRAMING PLAN: B-7 INDICATED ON PLAN (2 LOCATIONS) IS NOT IN BEAM SCHEDULE. PROVIDE.
4. SHEET S-2; ROOF FRAMING PLAN: PROVIDE GIRDER TRUSS LOADING DIAGRAM FOR MANUFACTURER.
5. SHEET S-2; HEADER SCHEDULE: PROVIDE HEADER DESIGNS IN CALCULATIONS.
6. SHEET S-2; SECTION 6/D-1: SECTION INDICATES POST CAP FOR SOLID BEAM. SHOW APPROPRIATE GIRDER TRUSS AND POST CAP.
7. SHEET S-2; SECTION 1/D-2 (AT GIRDER TRUSS): PROVIDE APPROPRIATE SECTION THROUGH GIRDER TRUSS. 1/D-2 IS AT EXTERIOR WALL.
8. SHEET D-2; SECTION 3: IS THIS SECTION RELEVANT TO THIS PROJECT? COULD NOT FIND SECTION CUT ON THE PLAN.
9. SHEET D-2; SECTION 12: CUT SECTION ON PLAN.

END OF REVIEW
01/14/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the energy code compliance using the components and areas based on the proposed building (e.g. calculations show only one door instead of 4 swinging doors and one sliding glass door, the roof insulation is installed in the cavity of the roof assembly not continuous, the slab is not insulated). Reference: Section 101.4, International Energy Conservation Code 2006.
2. Provide supporting documentation for the U-factors for the windows and the doors along with the SHGC for the windows and for the sliding door. Reference: Section 104.2, IECC 2006.
3. Provide manufacturer's equipment data along with mechanical and electrical operating information for the proposed heat pumps. Clarify the callouts for the heat pumps (i.e. the plans show only HP-1 being installed). Reference: Section 301.6, IMC 2006.
4. Provide the installed weight of the HVAC equipment. Reference: Section 106.3.1, IMC 2006
5. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
6. Provide maintenance access space for the fan coils. Reference: Section 304.1, IMC 2006.
7. Show the location and installed weight of the proposed condensing units. Reference: Section 106.3.1, IMC 2006.
8. Show the proposed locations for the bath exhaust fans. Clarify the purpose of the "Honney Well Vision Pro Thermostat" with respect to the bath exhaust fans. Reference: Section 106.3.1, IMC 2006.
01/16/2009 TERRY STEVENS ZONING REVIEW Denied 01/16/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
01/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; T09CM00065
APARTMENTS RE-FIT
3103 E ADAMS

THE ELECTRICAL PLANS FOR THIS PROJECT HAVE BEEN DENIED FOR THE FOLLOWING,

1. SERVICE HAS BEEN DRAWN INCORRECTLY, THE CONDUCTORS SUPPLYING 4 METER ENCLOSURE PROVIDES ONLY 205 AMPS,ALSO THE 8'' CONDUIT IS INCORRECT.
2.THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR IS INCORRECT.
3.UNDER CALCULATIONS,ONLY TWO APPLIANCE CIRCUITS REQUIRED.
4. THE RANGE SHOWS 11000 WATTS WHICH EQUALS 45.8 AMPS AT 240 VOLTS,THE 40 AMP CB IS TOO SMALL.
5. SHOW A DISCONNECT FOR COMPRESSORS.
6. 20 AMP CIRCUIT FOR HEAT PUMP IS QUESTIONABLE,SHOW CUT SHEET OR SPECIFICATION SHEET.
7. BED ROOM OUTLETS TO BE ARCH FAULT PROTECTED.
8.UNITS A AND D SHOW DRYERS BUT NO WASHERS, NOT REQUIRED BUT WHY A DRYER AND NO WASHER.
9. IN THE KITCHENS ALL COUNTER SPACES LARGER THAN 12" MUST HAVE A RECEPTACLE, ONE NOT SHOWN NEXT TO RANGE.
10. RISER DIAGRAM SHOWS SUB PANEL AS BEING 22/10 KAIC RATED, AT THE PANEL SCHEDULE IT'S ONLY RATED 10 KAIC,WHAT IS THE SHORT CIRCUIT CALCULATION AT THE SERVICE AND AT THE SUB-PANEL?
11. SHOW THE LOCATION OF THE TRANSFORMER FOR THE DOORBELL, CANNOT BE IN A CLOTHES CLOSET.
12.THE SWITCHING FOR THE PORCH LIGHT COMMON TO A -B -AND C SHOULD HAVE A 3-WAY SW IN A AND C,AND A 4- WAY IN B.

RAY T MAJUTA
DSD CITY OF TUCSON
ELECTRICAL PLAN CK
1/20/09
520-837-4988
01/23/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied Unable to approve building plan at this time. Please see site plan T08CM00065 and grading plan T08BU00523 R comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
02/02/2009 SUE REEVES REJECT SHELF Completed